RECOMMENDATIONS

· Fit burn out suction line drier /filter (temporary assemblies available)

· Use of acid neutralizing products is not recommended.

· Replace liquid line drier.

· Ensure oil failure switch operates-Remove compressor motor fuses and turn on control- to check DO not rely on SUCTION ACCUMULATOR to clean up liquid flood back – SUCTION SUPERHEAT must be calculated.

( most compressor failures are caused by liquid

refrigerant in the compressor.)

· System dryness and acid levels are most important particularly with polyester oils - change liquid line drier after approx 12 Hr COMPRESSOR running

check sight glass indicators and oil samples until satisfactory

(Oil analyzing available.)

· If the compressor failed and corrective measures have not been made the next compressor WILL fail – it is cheaper to fix the problem than keep replacing compressors.

title
                                                                                        home

grs banner

IMPORTANT  

INFORMATION

PLEASE READ BEFORE INSTALLING COMPRESSOR.

## Inspect compressor for damage and

missing components – if damaged

report it on the delivery docket and

advise Ganley Refrigeration.

## Check motor insulation and winding resistances’

## Check electrical connections are correct

for the application

SEE SKETCH BELOW

## Check correct oil is charged into

compressor for the application.

All compressors are supplied with Polyolester

as standard unless requested otherwise

SEE LABEL ON COMPRESSOR

## Check if oil cooler connection or head

cooling fan is required.

Some compressors must have the oil

cooler connected to enable lubrication of

the running gear

Back to top

AFTER INSTALLING

## Check motor electrical connections ,contactors,
and controls
Note. DWM and Copemetic have different
Thermister control relay units and part
winding configuration.
CONTACT GANLEY REFRIGERATION

## Check oil pressure(pump models) min
200kpa differential ( pump-suction)

## Check motor current draw
SEE NAME PLATE AMPS

## Check oil level-1/4 to 1/2 sight glass

## Check suction superheat(suction pressure
at compressor + 10Kpa converted to Temperature
subtract away suction line temperature at
the compressor inlet) use insulated probe of
known accuracy-
NOT LESS THAN 12oC